Quiz-summary
0 of 8 questions completed
Questions:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
Information
Premium Practice Questions
You have already completed the quiz before. Hence you can not start it again.
Quiz is loading...
You must sign in or sign up to start the quiz.
You have to finish following quiz, to start this quiz:
Results
0 of 8 questions answered correctly
Your time:
Time has elapsed
Categories
- Not categorized 0%
Unlock Your Full Report
You missed {missed_count} questions. Enter your email to see exactly which ones you got wrong and read the detailed explanations.
Submit to instantly unlock detailed explanations for every question.
Success! Your results are now unlocked. You can see the correct answers and detailed explanations below.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- Answered
- Review
-
Question 1 of 8
1. Question
A stakeholder message lands in your inbox: A team is about to make a decision about Testing and commissioning of MCCs as part of complaints handling at an audit firm, and the message indicates that a client is disputing the validity of the initial commissioning report for a new three-phase motor installation. The audit team must verify if the insulation resistance testing was conducted according to safety standards, specifically concerning the protection of integrated control circuits. With the final handover scheduled for tomorrow morning, the lead auditor needs to confirm the correct protocol for testing a Motor Control Center (MCC) that contains both heavy-duty contactors and sensitive electronic Variable Frequency Drives (VFDs). Which action should have been documented to ensure both the accuracy of the test and the integrity of the equipment?
Correct
Correct: Insulation resistance testing involves applying a high DC voltage (typically 500V for a 400V system). Sensitive electronic components like Variable Frequency Drives (VFDs) or PLCs within an MCC can be permanently damaged by this high voltage. Therefore, they must be disconnected or bridged out during the test to ensure the test voltage does not pass through their internal circuitry while still allowing the cables and busbars to be tested.
Incorrect: Applying 1000V DC is unnecessary for a standard 400V system and increases the risk of damaging insulation or components. Insulation resistance tests must always be performed on dead circuits, so testing while energized is a major safety violation and would damage the testing instrument. Phase-to-earth tests are a fundamental requirement of commissioning to ensure the safety of the installation and cannot be omitted.
Takeaway: Always isolate or protect sensitive electronic equipment before performing high-voltage insulation resistance tests on Motor Control Centers.
Incorrect
Correct: Insulation resistance testing involves applying a high DC voltage (typically 500V for a 400V system). Sensitive electronic components like Variable Frequency Drives (VFDs) or PLCs within an MCC can be permanently damaged by this high voltage. Therefore, they must be disconnected or bridged out during the test to ensure the test voltage does not pass through their internal circuitry while still allowing the cables and busbars to be tested.
Incorrect: Applying 1000V DC is unnecessary for a standard 400V system and increases the risk of damaging insulation or components. Insulation resistance tests must always be performed on dead circuits, so testing while energized is a major safety violation and would damage the testing instrument. Phase-to-earth tests are a fundamental requirement of commissioning to ensure the safety of the installation and cannot be omitted.
Takeaway: Always isolate or protect sensitive electronic equipment before performing high-voltage insulation resistance tests on Motor Control Centers.
-
Question 2 of 8
2. Question
A client relationship manager at an audit firm seeks guidance on Electrical Installation in Specific Environments as part of onboarding. They explain that during a technical audit of a manufacturing facility’s three-phase distribution network, a query arose regarding a balanced star-connected load. To verify that the installation aligns with fundamental electrical theory, the manager must determine the expected current in the neutral conductor under these balanced conditions.
Correct
Correct: In a balanced three-phase star (Wye) configuration, the three phase currents are equal in magnitude and separated by 120 degrees. When these currents meet at the star point, their vector (phasor) sum is zero, resulting in no current returning through the neutral conductor. This is a fundamental principle used to verify the efficiency and balance of industrial power systems.
Incorrect
Correct: In a balanced three-phase star (Wye) configuration, the three phase currents are equal in magnitude and separated by 120 degrees. When these currents meet at the star point, their vector (phasor) sum is zero, resulting in no current returning through the neutral conductor. This is a fundamental principle used to verify the efficiency and balance of industrial power systems.
-
Question 3 of 8
3. Question
A transaction monitoring alert at a wealth manager has triggered regarding Sensors (basic types and application) during control testing. The alert details show that the facility management team recently upgraded the lighting control system to include Passive Infrared (PIR) sensors to improve energy efficiency. During an internal audit of the building’s automated systems, it was noted that the PIR sensors in the high-traffic lobby are failing to trigger consistently during periods of high ambient temperature, despite being set to operate 24/7. Which characteristic of a PIR sensor is most likely responsible for this inconsistent performance?
Correct
Correct: Passive Infrared (PIR) sensors are passive devices that do not emit energy; instead, they detect infrared radiation (heat) emitted by objects. They function by identifying a change in the infrared energy levels across their segmented lens. When the ambient room temperature is close to the human body temperature (approximately 37 degrees Celsius), the thermal contrast between the person and the background is minimized, making it difficult for the sensor to detect movement.
Incorrect: The option regarding microwave pulses describes an active sensor that uses the Doppler effect, not a PIR sensor. The option regarding light-dependent resistors (LDRs) describes a photocell used for light-level detection (dusk-to-dawn) rather than motion detection. The option regarding ultrasonic frequencies describes ultrasonic sensors, which use sound waves and are susceptible to acoustic interference, whereas PIR sensors are purely optical/thermal.
Takeaway: PIR sensors rely on thermal contrast between a moving object and the background environment to trigger, making them less effective when ambient temperatures approach human body temperature.
Incorrect
Correct: Passive Infrared (PIR) sensors are passive devices that do not emit energy; instead, they detect infrared radiation (heat) emitted by objects. They function by identifying a change in the infrared energy levels across their segmented lens. When the ambient room temperature is close to the human body temperature (approximately 37 degrees Celsius), the thermal contrast between the person and the background is minimized, making it difficult for the sensor to detect movement.
Incorrect: The option regarding microwave pulses describes an active sensor that uses the Doppler effect, not a PIR sensor. The option regarding light-dependent resistors (LDRs) describes a photocell used for light-level detection (dusk-to-dawn) rather than motion detection. The option regarding ultrasonic frequencies describes ultrasonic sensors, which use sound waves and are susceptible to acoustic interference, whereas PIR sensors are purely optical/thermal.
Takeaway: PIR sensors rely on thermal contrast between a moving object and the background environment to trigger, making them less effective when ambient temperatures approach human body temperature.
-
Question 4 of 8
4. Question
A regulatory guidance update affects how a fund administrator must handle Specific requirements for sensitive electronic equipment in the context of outsourcing. The new requirement implies that when evaluating a third-party data center’s electrical infrastructure, the internal auditor must verify the implementation of measures to mitigate the effects of non-linear loads. During a site visit scheduled for the next fiscal quarter, which design feature should the auditor prioritize to ensure the protection of sensitive microprocessor-based equipment from harmonic distortion and neutral overheating?
Correct
Correct: Sensitive electronic equipment typically utilizes switched-mode power supplies (SMPS), which are non-linear loads. These loads generate triplen harmonics (3rd, 9th, 15th, etc.) that do not cancel out in the neutral conductor of a three-phase system. Instead, these currents add up in the neutral, potentially leading to overheating and equipment failure. Using oversized or double-rated neutral conductors is a standard requirement to safely manage these additive currents.
Incorrect: Increasing the primary supply voltage is an incorrect approach as it does not address harmonic distortion and may lead to overvoltage damage to sensitive components. Type AC RCDs are often unsuitable for modern electronic equipment because they may fail to trip in the presence of DC components in the fault current; Type A or B RCDs are generally preferred. Placing any form of high-impedance filter in the main earthing conductor is a major safety violation, as it increases the earth fault loop impedance and could prevent protective devices from operating within the required disconnection times.
Takeaway: Sensitive electronic equipment requires specific electrical design considerations, such as oversized neutrals, to handle the unique harmonic profiles and non-linear current demands of modern power supplies.
Incorrect
Correct: Sensitive electronic equipment typically utilizes switched-mode power supplies (SMPS), which are non-linear loads. These loads generate triplen harmonics (3rd, 9th, 15th, etc.) that do not cancel out in the neutral conductor of a three-phase system. Instead, these currents add up in the neutral, potentially leading to overheating and equipment failure. Using oversized or double-rated neutral conductors is a standard requirement to safely manage these additive currents.
Incorrect: Increasing the primary supply voltage is an incorrect approach as it does not address harmonic distortion and may lead to overvoltage damage to sensitive components. Type AC RCDs are often unsuitable for modern electronic equipment because they may fail to trip in the presence of DC components in the fault current; Type A or B RCDs are generally preferred. Placing any form of high-impedance filter in the main earthing conductor is a major safety violation, as it increases the earth fault loop impedance and could prevent protective devices from operating within the required disconnection times.
Takeaway: Sensitive electronic equipment requires specific electrical design considerations, such as oversized neutrals, to handle the unique harmonic profiles and non-linear current demands of modern power supplies.
-
Question 5 of 8
5. Question
The risk committee at a fintech lender is debating standards for Testing and certification of fire alarm systems as part of record-keeping. The central issue is that the facility’s maintenance logs show frequent weekly tests, but there is no evidence of a professional periodic review within the last 12 months. To ensure the system meets the requirements for a commercial installation and maintains the validity of the firm’s professional indemnity insurance, what specific certification must be obtained?
Correct
Correct: In accordance with BS 5839, commercial fire alarm systems require periodic inspection and servicing by a competent person. This process results in a certificate of inspection and servicing, which is the primary document used for record-keeping to prove the system is being maintained in a functional state and remains compliant with safety standards.
Incorrect: A verification certificate from a fire authority is not a standard maintenance document, as fire authorities typically inspect for enforcement rather than providing service certification. A design certificate is only issued during the initial planning phase of the system. An installation certificate confirms the initial wiring and setup but does not satisfy the requirement for ongoing periodic testing and functional verification.
Takeaway: Commercial fire alarm systems must be professionally inspected and certified periodically by a competent person to ensure ongoing compliance and safety.
Incorrect
Correct: In accordance with BS 5839, commercial fire alarm systems require periodic inspection and servicing by a competent person. This process results in a certificate of inspection and servicing, which is the primary document used for record-keeping to prove the system is being maintained in a functional state and remains compliant with safety standards.
Incorrect: A verification certificate from a fire authority is not a standard maintenance document, as fire authorities typically inspect for enforcement rather than providing service certification. A design certificate is only issued during the initial planning phase of the system. An installation certificate confirms the initial wiring and setup but does not satisfy the requirement for ongoing periodic testing and functional verification.
Takeaway: Commercial fire alarm systems must be professionally inspected and certified periodically by a competent person to ensure ongoing compliance and safety.
-
Question 6 of 8
6. Question
A procedure review at an audit firm has identified gaps in Electrical Installation for Project Documentation and Handover as part of regulatory inspection. The review highlights that several industrial sites utilizing three-phase induction motors lacked updated schematics upon project completion. When handing over a project involving a new three-phase distribution board and associated motor control gear, why is it essential to provide the client with a comprehensive schedule of test results and manufacturer instructions?
Correct
Correct: Providing a complete set of documentation, including test results and manufacturer instructions, is a regulatory requirement that ensures the client has the necessary information for the safe operation and ongoing maintenance of the system. It allows future electrical workers to understand the circuit configurations and safety characteristics, which is essential for risk management and compliance with safety legislation.
Incorrect
Correct: Providing a complete set of documentation, including test results and manufacturer instructions, is a regulatory requirement that ensures the client has the necessary information for the safe operation and ongoing maintenance of the system. It allows future electrical workers to understand the circuit configurations and safety characteristics, which is essential for risk management and compliance with safety legislation.
-
Question 7 of 8
7. Question
Following an on-site examination at a credit union, regulators raised concerns about Testing and certification of Ex installations in the context of outsourcing. Their preliminary finding is that the internal audit department failed to adequately assess the third-party contractor’s compliance with specialized safety standards for hazardous areas, such as fuel storage for backup generators. Which of the following actions should the internal auditor prioritize to address this deficiency and ensure the integrity of the Ex installation certifications?
Correct
Correct: Internal auditors must ensure that specialized work in hazardous areas is performed by competent persons. Verifying specific certifications like CompEx and ensuring that inspection records match the specific protection concepts (such as flameproof or increased safety) is essential to confirm that the outsourced provider is meeting the technical requirements for Ex installations.
Incorrect: Focusing on financial penalties in a service level agreement addresses performance and timeliness but does not validate the technical safety or certification compliance of the work. Relying on insurance coverage is a risk transfer strategy that does not address the underlying control failure regarding safety standards. General staff walkthroughs are insufficient because Ex installations require specialized knowledge, tools, and techniques that general personnel do not possess.
Takeaway: Auditing outsourced hazardous area maintenance requires verifying the technical competency of the provider and the alignment of their documentation with specific safety standards.
Incorrect
Correct: Internal auditors must ensure that specialized work in hazardous areas is performed by competent persons. Verifying specific certifications like CompEx and ensuring that inspection records match the specific protection concepts (such as flameproof or increased safety) is essential to confirm that the outsourced provider is meeting the technical requirements for Ex installations.
Incorrect: Focusing on financial penalties in a service level agreement addresses performance and timeliness but does not validate the technical safety or certification compliance of the work. Relying on insurance coverage is a risk transfer strategy that does not address the underlying control failure regarding safety standards. General staff walkthroughs are insufficient because Ex installations require specialized knowledge, tools, and techniques that general personnel do not possess.
Takeaway: Auditing outsourced hazardous area maintenance requires verifying the technical competency of the provider and the alignment of their documentation with specific safety standards.
-
Question 8 of 8
8. Question
The compliance framework at a private bank is being updated to address Response to Electric Shock as part of risk appetite review. A challenge arises because the bank’s internal audit department has identified that the 24-hour data center staff are not adequately trained in emergency procedures. During a simulated safety drill, a technician is found in contact with a live 400V busbar. To prevent further injury or fatality, what is the primary action the first responder must take before attempting to provide first aid?
Correct
Correct: The fundamental principle of responding to an electric shock is to ensure the safety of the rescuer. The power source must be isolated to stop the flow of current. If isolation is not possible, a dry, non-conductive object must be used to break the contact. This prevents the rescuer from also becoming a victim of the electric shock.
Incorrect
Correct: The fundamental principle of responding to an electric shock is to ensure the safety of the rescuer. The power source must be isolated to stop the flow of current. If isolation is not possible, a dry, non-conductive object must be used to break the contact. This prevents the rescuer from also becoming a victim of the electric shock.